EXINDA FLEX 118 kW R515B Water-to-Water Scroll Heat Pump Chiller


Water-source comfort for commercial projects.

Adapt water-source heating and cooling to the building with EXINDA FLEX. The 118 kW R515B scroll heat pump chiller provides cooling, heating and high-temperature hot-water duties for commercial and institutional projects. Multi-unit sequencing supports system integration.

Core specifications

Product configuration
ItemPublished data
SystemEXINDA FLEX water-to-water scroll heat pump chiller
FunctionsHydronic cooling, heating and high-temperature heating
RefrigerantR515B; GWP 293; 22.7 kg charge
Compressors and circuits2 scroll compressors; 2 refrigerant circuits
Heat exchangersShell-and-tube evaporator and condenser; S316L stainless-steel water-side material
Power and current380 V / 3 Ph / 50 Hz; 52.2 A cooling; 70.9 A heating
Water connections3 in. condenser; 2.5 in. evaporator, inlet and outlet
Net dimensions1991 × 1389 × 1740 mm (L × W × H)
Weight1,300 kg machine; 1,380 kg operating
Sound pressure85 dB(A), referenced at 1 m

Cooling and Heating Performance

Performance at the stated water conditions
Operating modePublished capacityInput / efficiencyRated water temperatures
Cooling118 kW29.27 kW input; EER 4.01 W/WLoad side 12.2/6.7°C; source side 29.4/34.6°C
Heating186 kW46.51 kW input; COP 4.03 W/WLoad side 24.6/18.3°C; source side 48.9/60.0°C
High-temperature heating175 kW66.85 kW inputLoad side 25.0/20.0°C; source side 70.0/80.0°C

Hydronics and controls

Published water-flow data
ConditionEvaporator sideCondenser sidePressure-drop evidence
Rated cooling18.3 m³/h24.96 m³/hNot stated
Rated heating19.3 m³/h15.08 m³/hNot stated
High-temperature heatingNot statedNot statedNot stated

Control package

PLC-based control, 7-inch HMI touchscreen, Modbus RTU/TCP and BACnet through a gateway are listed. Multi-unit sequencing is stated for up to six units.

Technical Documents and Related Products

Download the technical submittal ↓PDF · Performance, water conditions, electrical data and dimensional information

Water-Source Heat Pump Selection Questions

Which projects suit a water-source heat pump chiller?

Commercial buildings, institutions and industrial projects with a suitable water loop or available heat source can use a water-source system for hydronic heating and cooling.

Can it support a boiler upgrade?

Yes. High-temperature hot-water operation can support building heating upgrades. Match the water-source conditions and heating temperatures to the existing distribution system.

What should I send for initial selection?

Share the project location, heating or cooling load and the available water-source temperatures. EXINDA can help identify the configuration and technical package for the next design stage.

Partner With EXINDA

Distributors & Dealers

Expand your HVAC offering with EXINDA heat pumps and ventilation systems, backed by product training and technical support.

Engineering Firms & Contractors

Get the performance data, submittals and engineering support you need to select equipment and move your project forward.

HVAC Brands

Bring your product ideas to market with EXINDA’s engineering, testing and manufacturing expertise.