EXINDA FLEX 45 kW R290 Modular Air-to-Water Heat Pump


Capacity that fits the building.

Plan year-round hydronic comfort for smaller commercial buildings with EXINDA FLEX 45 kW R290 heat pump. Supply heating in winter and chilled water in summer, with a modular configuration that can grow with the project. A natural-refrigerant option for offices, hospitality buildings and commercial renovations.

Core Specifications

FBMBHT4B2E3
Core specifications for FBMBHT4B2E3
Nominal capacity and rated conditionHeating: 45 kW at 7/6°C outdoor DB/WB and 35°C leaving water. Cooling: 34 kW at 35/24°C outdoor DB/WB and 7°C leaving water.
Published capacity range12.8–47.3 kW heating; 10.8–36.2 kW cooling
Published electrical input range3.316–10.534 kW heating; 3.942–11.138 kW cooling
Published COP / EER rangeCOP 3.86–4.49; EER 2.74–3.25
RefrigerantR290; 3.5 kg charge; GWP stated as 3
Power supply and protection380–400 V / 50 Hz / 3 Ph; R, S, T, N and Ground; MCA 40 A; MOP 50 A
Published operating rangesAmbient −25 to 43°C; heating leaving water 35–60°C; cooling leaving water 7–27°C
Water circuit7.7 m³/h published flow; G 2 in. female-thread inlet and outlet
Sound pressure65 / 61 / 58 dB(A), Daytime Max / Rated / Low Noise; stated as converted at 1 m
Dimensions and weight1135 × 1035 × 2118 mm (L × W × H); net 400 kg. Shipping: 1195 × 1095 × 2197 mm; 450 kg.
CompressorDC inverter
Published control functionsStandby anti-freeze, demand-based defrost and cascade connection for up to eight units

Heating Performance

Published full-condition heating data at 55°C leaving-water temperature. Outdoor temperatures below are dry-bulb values.

Heating performance at 55 degrees Celsius leaving-water temperature
Outdoor air DBHeating capacityInput powerCOP
8°C43.086 kW14.529 kW2.97
2°C39.897 kW14.460 kW2.76
−12°C34.870 kW15.640 kW2.23
−25°C25.761 kW15.985 kW1.61

Technical Documents

Modular Heat Pump Chiller Selection Questions

Where does a two-pipe system fit best?

A two-pipe system suits buildings whose connected zones can share a heating or cooling mode. It supplies hot water in heating mode and chilled water in cooling mode.

Can it be used in a boiler upgrade?

Yes. It can provide electric hydronic heating and chilled-water cooling with suitable terminals. An existing boiler can remain as supplementary or backup heat in the system design.

How do I choose the capacity for my building?

Use the building’s heating and cooling loads and required water temperatures to select the unit capacity and number of modules.

What should I send to start a project discussion?

Share the location, building use and the capacity you are considering. EXINDA can help compare configurations and provide the technical package for the next design step.

Colabore con EXINDA

Fabricante global de climatización y proveedor de soluciones personalizadas

EXINDA es un fabricante global de climatización especializado en bombas de calor, sistemas de ventilación y soluciones climáticas personalizadas para aplicaciones residenciales y comerciales.

Colaboramos con distribuidores, ingenieros, contratistas y socios OEM de todo el mundo.

1. Distribuidores y comerciantes de climatización
Apoyamos a nuestros socios de todo el mundo con soluciones fiables de bombas de calor y ventilación.

2. Empresas de ingeniería y contratistas
Proporcionamos documentación técnica, asistencia para la selección de productos y apoyo a proyectos.

3. Socios OEM / ODM
Ofrecemos soluciones de climatización personalizadas, fabricación con marca privada y apoyo al desarrollo de productos.