EXINDA Aura 25,000 Btu/h Vertical Stack Plus Heat Pump ERV (HPERV)


HIGHER-CAPACITY VERTICAL-STACK HEATING, COOLING AND FRESH AIR

EXINDA AURA Vertical Stack Plus is a higher-capacity 60 Hz all-in-one heat pump ERV for apartments, multifamily buildings and multi-room applications where a ceiling-mounted unit is not feasible. The vertical indoor cabinet integrates heating, cooling and fresh-air functions without a conventional outdoor condensing unit for each dwelling.

25,000 Btu/hRated cooling at 95°F
21,300 Btu/hHeating table value at 47°F
280–850 CFMIndoor airflow range
208–230 V / 60 Hz / 1 PhHardwired supply

Is this the right Vertical Stack Plus unit?

  • Loads fit the verified capacity at the project design temperatures.
  • Vertical wall space, exterior air paths and indoor ducts can be coordinated.
  • Structural support for 470 lb, 3 kW auxiliary heat and condensate routing are accounted for.

Separate balanced-ERV airflow data is pending confirmation.

Core Specifications

System typeHigher-capacity vertical-stack all-in-one heat pump energy recovery ventilator
Rated cooling25,000 Btu/h; EER 11.65 at 95°F outdoor / 80°F indoor rating conditions
Heating table21,300 Btu/h at 47°F; 12,800 Btu/h at 23°F; 10,200 Btu/h at 5°F
Heating COP3.56 at 47°F; 2.37 at 23°F; 2.01 at 5°F
Indoor airflow / ESP280–850 CFM / 0.32 in. w.g. (80 Pa)
Outdoor airflow / ESP450–1,320 CFM / 0.80 in. w.g. (200 Pa)
Outdoor connections8 in. round intake and exhaust
Power supply208–230 V / 60 Hz / 1 Ph, hardwired
MCA / MOP30 A / 35 A
Auxiliary heat / max inputUp to 3 kW / 3,900 W
Compressor / refrigerantBLDC twin-rotary inverter / R32 A2L
Refrigerant chargeNot stated in the supplied submittal
Operating rangeHeat-pump compressor 5 to 109°F
Sound pressure48 dB(A) at 1 m; 43 dB(A) at 3 m
Indoor filterMERV 3
Dimensions / weight32 × 24 × 84 in. / 470 lb
Data confirmation: The cover lists 19,000 Btu/h heating while the detailed table lists 21,300 Btu/h at 47°F. This page uses the condition-specific table. Balanced ERV airflow, refrigerant charge and complete model number also require confirmation.
Evidence boundary: No AHRI, UL, CSA, HVI or other product certification is claimed on this page.

Heating, Cooling and Airflow Performance

Use the condition-specific capacity table. Do not treat the outdoor-airflow range as a confirmed balanced ventilation rate.

Operating pointCapacity / airflowInput / efficiencyCondition
Cooling25,000 Btu/h2,140 W; EER 11.6595°F outdoor / 80°F indoor
Heating21,300 Btu/h1,750 W; COP 3.5647°F outdoor
Low-temperature heating12,800 Btu/h1,590 W; COP 2.3723°F outdoor
Minimum compressor condition10,200 Btu/h1,490 W; COP 2.015°F outdoor
Indoor airflow280–850 CFMUp to 0.32 in. w.g.
Outdoor airflow450–1,320 CFMUp to 0.80 in. w.g.

Source: supplied EXINDA AURA 25K Vertical Stack Plus HPERV submittal.

Technical Documents

Questions Before You Specify

Is 450–1,320 CFM the balanced ventilation rate?

The supplied document does not provide a separate balanced ERV performance table. Confirm the required fresh-air and exhaust airflow before selection.

Which heating capacity should be used?

Use the condition-specific table: 21,300 Btu/h at 47°F, 12,800 Btu/h at 23°F and 10,200 Btu/h at 5°F. The front-page headline differs and is pending confirmation.

What happens below 5°F?

The compressor is disabled below 5°F and up to 3 kW auxiliary heat remains. Confirm the design load against the available auxiliary capacity.

How is Vertical Stack Plus different?

It provides higher cooling capacity and airflow in a larger 470 lb cabinet. Load, duct, wall-space, access and structural checks are independent.

What should an enquiry include?

Provide room loads, design temperatures, ventilation airflow, duct static pressure, service space, electrical supply, condensate route, quantity and schedule.

Request selection support or a quote

For the 25,000 Btu/h Vertical Stack Plus HPERV, provide zone loads, design temperatures, required balanced ventilation airflow and duct static pressure.

Also include wall/service space, structural support for 470 lb, 208–230 V electrical capacity, 3 kW auxiliary heat, condensate route, quantity and schedule.